What a battery can sell
What ancillary services can a battery sell in Single Electricity Market (SEM)?
Single Electricity Market (SEM) has 14 ancillary-service products, across 7 families — fast frequency response, manual frequency restoration, contingency reserve, ramping reserve, replacement reserve, inertia & system strength and reactive power & voltage: Dynamic Reactive Response, Fast Frequency Response, Fast Post-Fault Active Power Recovery, Primary Operating Reserve, Ramping Margin 1, Ramping Margin 3, Ramping Margin 8, Replacement Reserve De-synchronised, and 6 more. Response timing, direction and eligibility for each are in the cards below, as the official sources state them.
Facts below are stated as the official sources state them. A missing line means the
source does not state that value — never that the value is zero.
Fast frequency response
-
Fast Frequency Response
operational
Deliver very fast active-power response after a frequency event.
- Direction
- upward or downward according to contract
- Trigger / range
- frequency event under DS3 performance methodology
- Eligibility
- qualified generating units, demand-side units, storage and other service providers meeting DS3 tests
- Typical procurement
- Dynamic or not publicly stated
- Pricing
- regulated/tariff and contractual arrangements under the DS3 ruleset
The 2-10 second interval is the product measurement window, not a stated maximum dispatch duration.
Manual frequency restoration
-
Tertiary Operating Reserve 1
operational
Provide the first slower layer of tertiary post-contingency reserve.
- Direction
- primarily upward response
- Trigger / range
- contingency/dispatch need
- Eligibility
- DS3-qualified providers
- Typical procurement
- Dynamic or not publicly stated
- Pricing
- DS3 tariff/contract rules
The 90-second to five-minute interval is a measurement window.
-
Tertiary Operating Reserve 2
operational
Provide longer post-contingency tertiary reserve and release faster products.
- Direction
- primarily upward response
- Trigger / range
- contingency/dispatch need
- Eligibility
- DS3-qualified providers
- Typical procurement
- Dynamic or not publicly stated
- Pricing
- DS3 tariff/contract rules
The five-to-20-minute interval is a measurement window.
Contingency reserve
-
Primary Operating Reserve
operational
Arrest frequency decline immediately after a contingency.
- Direction
- primarily upward response
- Trigger / range
- frequency event
- Eligibility
- DS3-qualified providers
- Typical procurement
- Dynamic or not publicly stated
- Pricing
- DS3 tariff/contract rules
The 5-15 second interval is a measurement window.
-
Secondary Operating Reserve
operational
Sustain and deepen post-contingency reserve after POR.
- Direction
- primarily upward response
- Trigger / range
- frequency event
- Eligibility
- DS3-qualified providers
- Typical procurement
- Dynamic or not publicly stated
- Pricing
- DS3 tariff/contract rules
The 15-90 second interval is a measurement window.
Ramping reserve
-
Ramping Margin 1
operational
Reward upward and downward ramp capability available over the next hour.
- Direction
- upward and downward
- Trigger / range
- forecast ramp and system need
- Eligibility
- DS3-qualified providers
- Typical procurement
- Dynamic or not publicly stated
- Pricing
- DS3 tariff/contract rules
One hour is the ramp horizon, not a fault-response deadline.
-
Ramping Margin 3
operational
Reward ramp capability over a three-hour horizon.
- Direction
- upward and downward
- Trigger / range
- forecast ramp and system need
- Eligibility
- DS3-qualified providers
- Typical procurement
- Dynamic or not publicly stated
- Pricing
- DS3 tariff/contract rules
Three hours is the ramp horizon.
-
Ramping Margin 8
operational
Reward ramp capability over an eight-hour horizon.
- Direction
- upward and downward
- Trigger / range
- forecast ramp and system need
- Eligibility
- DS3-qualified providers
- Typical procurement
- Dynamic or not publicly stated
- Pricing
- DS3 tariff/contract rules
Eight hours is the ramp horizon.
Replacement reserve
-
Replacement Reserve De-synchronised
operational
Provide replacement reserve from resources not synchronized at the event start.
- Direction
- upward
- Trigger / range
- TSO dispatch requirement
- Eligibility
- qualified de-synchronized providers
- Typical procurement
- Dynamic or not publicly stated
- Pricing
- DS3 tariff/contract rules
The cited sources do not give one unambiguous response time across RRD arrangements, so none is shown.
-
Replacement Reserve Synchronised
operational
Provide replacement reserve from units already synchronized after faster reserves are depleted.
- Direction
- upward
- Trigger / range
- TSO dispatch requirement
- Eligibility
- qualified synchronized providers
- Typical procurement
- Dynamic or not publicly stated
- Pricing
- DS3 tariff/contract rules
Twenty minutes to one hour is the DS3 performance interval, not a universal activation schedule.
Inertia & system strength
Reactive power & voltage
-
Dynamic Reactive Response
operational
Provide rapid dynamic reactive current/power support during voltage disturbances.
- Direction
- reactive injection or absorption
- Trigger / range
- voltage disturbance under DS3 technical tests
- Eligibility
- qualified providers meeting dynamic reactive response tests
- Typical procurement
- Dynamic or not publicly stated
- Pricing
- DS3 tariff/contract rules
No single response time is published without the detailed test procedure.
-
Fast Post-Fault Active Power Recovery
operational
Restore active power rapidly after voltage recovery from a transmission fault.
- Direction
- active-power restoration
- Trigger / range
- after terminal voltage has recovered to at least 85% of nominal
- Eligibility
- qualified wind and other applicable nonsynchronous units meeting fault-recovery tests
- Typical procurement
- Dynamic or not publicly stated
- Pricing
- DS3 tariff/contract rules
The 250 ms criterion is measured after voltage recovery, not necessarily from fault inception; no response-duration value is inferred.
-
Steady State Reactive Power
operational
Maintain voltage by supplying or absorbing steady-state reactive power.
- Direction
- reactive power injection and absorption
- Trigger / range
- voltage-control instruction and capability curve
- Eligibility
- qualified providers meeting reactive capability tests
- Typical procurement
- Dynamic or not publicly stated
- Pricing
- DS3 tariff/contract rules
Reactive power is normally measured in MVAr; MW procurement range is not applicable.