Germany (VDE-AR-N 4120, draft summary) ride-through requirements

High-voltage ride-through, Frequency ride-through for Germany. Every breakpoint below is read from the code itself, and where a point was taken off a published figure rather than stated in the clause, the section under that chart says so — an envelope the source only partly defines, an envelope that stops where its published chart stops or a table read from a reproduction.

2Envelopes
HVRT · FRTEvents
Transmission & distribution Connection level
110 kV high-voltage network Applicability boundary
HVRT

What is the high-voltage ride-through envelope for Germany (VDE-AR-N 4120, draft summary)?

The plant must ride through for any voltage that stays on or below this envelope. The envelope holds 1.3 pu from t = 0 to 100 ms; then 1.25 pu from 100 ms to 60 s; then 1.15 pu from 60 s onward — the last band the envelope defines, with no stated end time.

Covers only the part of the envelope the source defines. Read from a reproduction of the table rather than the standard itself, and cross-checked against the other codes cited below.

Applies to Customer installations on the 110 kV high-voltage network, including storage (draft scope)

Germany (VDE-AR-N 4120, draft summary) — high-voltage ride-through envelopeGermany (VDE-AR-N 4120, draft summary) high-voltage ride-through envelope. The plant must ride through for any voltage that stays on or below the line; above it, the envelope no longer applies. Logarithmic time axis from 0.01 s to 200 s; linear voltage axis in per-unit. The first band applies from the instant of the event (t = 0). The envelope holds 1.3 pu from t = 0 to 100 ms; then 1.25 pu from 100 ms to 60 s; then 1.15 pu from 60 s onward — the last band the envelope defines, with no stated end time (drawn as an open dashed tail). Read from a reproduction of the table, not the standard itself.Germany (VDE-AR-N 4120, draft summary) — high-voltage ride-through envelopeRead from a reproduction of the table, not the standard itselfnominal 1.00 pu0.010.11101000.901.001.101.201.301.40Time from event start (s, log scale) · first band applies from t = 0Voltage (pu)1.15 puMUST RIDE THROUGHmust ride through on or below the lineopen — no stated end time
High-voltage ride-through envelope for Germany (VDE-AR-N 4120, draft summary). Time runs on a logarithmic axis. Scroll the chart sideways for the rest of the time axis →
High-voltage ride-through breakpoints for Germany (VDE-AR-N 4120, draft summary)
From To Voltage Between the points
0 100 ms 1.3 pu Held flat
100 ms 60 s 1.25 pu Held flat
60 s no stated end 1.15 pu Held flat
The clause this came from

FNN/VDE 'Summary of the draft VDE-AR-N 4120:2017-05' (Forum Netztechnik/Netzbetrieb im VDE, May 2017). READ THIS BEFORE USING THE NUMBERS: it is a summary of a DRAFT (E VDE-AR-N 4120), it states on its own first page that it 'does not cover all parts of the VDE-AR-N 4120 and is therefore not exhaustive' and is 'purely informative', and it has since been superseded twice — by VDE-AR-N 4120:2018-11 and amendment A1:2024-04. Values may have changed on publication. Slide 19 (Type 1 modules, upper limit curve) read together with slide 21, whose prose states the surge requirement is 'unchanged compared to AR-N-4120-2015 (after 60s to U=1.15)'. The 1.25 pu level is corroborated a third time by the protection table on slide 48, where the generating-unit setting is U>> 1.25 UNS at 0.1 s. Published because three statements in the document agree, not because the chart alone was legible. Low-voltage ride-through is deliberately not included for this code. The LVRT curves exist only as chart images here, and two earlier candidate readings were wrong in ways worth naming: 4110 and 4120 LVRT curves that were byte-identical across different voltage levels, which no real code does, and a 'high-voltage' curve that was really a VDN-2004 voltage-relay setting. That second substitution is visible in this very document, which prints the relay table beside the curves — the tables are crisp and the curves are images, so the legible thing gets digitised. Protection settings say when a plant MAY disconnect; a ride-through envelope says when it MUST NOT. Plotting LVRT needs VDE-AR-N 4120:2018-11 itself, ideally with A1:2024-04.

FRT

What is the frequency ride-through envelope for Germany (VDE-AR-N 4120, draft summary)?

The plant must ride through between the upper and lower bands. The upper (over-frequency) band holds 51.5 Hz from t = 0, plotted to 60 min. The lower (under-frequency) band holds 47.5 Hz from t = 0, plotted to 60 min. Correction: one band here stops at the published chart’s window while the clause quoted below states continuous operation across the same range — where the two disagree, the clause governs.

Covers only the part of the envelope the source defines. The envelope stops where the published chart stops; the code states no end time. Read from a reproduction of the table, not from the standard itself.

Applies to Customer installations on the 110 kV high-voltage network, including storage (draft scope)

Germany (VDE-AR-N 4120, draft summary) — frequency ride-through envelopeGermany (VDE-AR-N 4120, draft summary) frequency ride-through envelope. The plant must ride through for any frequency that stays between the lower and upper bands. Logarithmic time axis from 100 s to 5000 s; linear frequency axis in hertz. The first band applies from the instant of the event (t = 0). upper (over-frequency) band: holds 51.5 Hz from t = 0, plotted to 60 min. lower (under-frequency) band: holds 47.5 Hz from t = 0, plotted to 60 min. Stops where the published chart stops — the code states no end time.Germany (VDE-AR-N 4120, draft summary) — frequency ride-through envelopeStops where the published chart stops — the code states no end timenominal 50 Hz10010002005002000474849505152Time from event start (s, log scale) · first band applies from t = 0Frequency (Hz)51.5 Hzplotted to 60 min47.5 Hzplotted to 60 minMUST RIDE THROUGHUpper band (over-frequency)Lower band (under-frequency)must ride through between the bandsends at the plotted window, not a stated limit
Frequency ride-through envelope for Germany (VDE-AR-N 4120, draft summary). Time runs on a logarithmic axis. Scroll the chart sideways for the rest of the time axis →

Upper limit

Frequency ride-through breakpoints for Germany (VDE-AR-N 4120, draft summary) — Upper limit
From To Frequency Between the points
0 plotted to 60 min 51.5 Hz Held flat

Lower limit

Frequency ride-through breakpoints for Germany (VDE-AR-N 4120, draft summary) — Lower limit
From To Frequency Between the points
0 plotted to 60 min 47.5 Hz Held flat
The clause this came from

FNN/VDE 'Summary of the draft VDE-AR-N 4120:2017-05' (Forum Netztechnik/Netzbetrieb im VDE, May 2017). READ THIS BEFORE USING THE NUMBERS: it is a summary of a DRAFT (E VDE-AR-N 4120), it states on its own first page that it 'does not cover all parts of the VDE-AR-N 4120 and is therefore not exhaustive' and is 'purely informative', and it has since been superseded twice — by VDE-AR-N 4120:2018-11 and amendment A1:2024-04. Values may have changed on publication. Slide 51, tabular: for VDE-AR-N 4120 (new), at or below 47.5 Hz isolation from the grid, between 47.5 and 51.5 Hz 'isolation not permitted', between 51.5 and 52.5 Hz isolation PERMITTED, and at 52.5 Hz isolation from the grid. Plotted here is the firm obligation only — the 47.5 to 51.5 Hz band, which carries no time limit. The 51.5 to 52.5 Hz shoulder is discretionary and is deliberately not drawn as a requirement. The matching generating-unit protection settings on the same slide are f< 47.5 Hz at 0.1 s, f> 51.5 Hz at up to 5 s, and f>> 52.5 Hz at 0.1 s. Low-voltage ride-through is deliberately not included for this code. The LVRT curves exist only as chart images here, and two earlier candidate readings were wrong in ways worth naming: 4110 and 4120 LVRT curves that were byte-identical across different voltage levels, which no real code does, and a 'high-voltage' curve that was really a VDN-2004 voltage-relay setting. That second substitution is visible in this very document, which prints the relay table beside the curves — the tables are crisp and the curves are images, so the legible thing gets digitised. Protection settings say when a plant MAY disconnect; a ride-through envelope says when it MUST NOT. Plotting LVRT needs VDE-AR-N 4120:2018-11 itself, ideally with A1:2024-04.

This row stops at the chart window, and the clause does not. One band here stops at a fixed time, while the clause above speaks of continuous operation across the same range — and the other band of the same row has no stated end. Where the chart and the clause disagree, the clause governs.

Scope

Who does Germany (VDE-AR-N 4120, draft summary) bind, and since when?

Customer installations on the 110 kV high-voltage network, including storage (draft scope). Draft 2017-05; superseded by 4120:2018-11 and A1:2024-04.

These figures are a reading aid, not legal advice. Grid codes are reissued: verify against the current edition before you design to them.

Digitised operating parameters beyond ride-through — droop, reactive capability, operating ranges — are published for 36 of the 66 codes in this atlas, not yet for Germany (VDE-AR-N 4120, draft summary). That is a gap on this site, not a statement that Germany (VDE-AR-N 4120, draft summary) sets none — the atlas hub marks the codes that carry them.

Curve data last checked against the code on — 66 standards, 130 envelopes, published by bess.engineer under CC BY 4.0.

Questions

Questions this page answers about Germany (VDE-AR-N 4120, draft summary)

Does Germany (VDE-AR-N 4120, draft summary) require ride-through, or only that the plant does not trip?
Ride-through, for the envelopes on this page — that is what each of them is. It is not everything Germany (VDE-AR-N 4120, draft summary) contains: the clauses quoted under the charts also address when the plant may or must trip. The requirement sentence under each chart says which side of the curve is the compliant one.
Are the numbers on this page taken from Germany (VDE-AR-N 4120, draft summary) itself?
Every breakpoint is read from the code, and where a point was taken off a published figure rather than stated in the clause, the section under that chart says so — on this page that includes an envelope the source only partly defines, an envelope that stops where its published chart stops or a table read from a reproduction. The clause each curve came from is quoted under it.
Which events are charted for Germany (VDE-AR-N 4120, draft summary)?
Germany (VDE-AR-N 4120, draft summary) is charted here with 2 envelopes — high-voltage ride-through, frequency ride-through (HVRT, FRT). No low-voltage envelope is charted here — check Germany (VDE-AR-N 4120, draft summary) itself before concluding it sets none.
Related

Ride-through, in context.

An envelope is a compliance boundary; understanding why it exists is a different question. The ride-through and grid-forming entries cover the engineering, and the Engineering Foundations course builds it from the physics up.

Elsewhere in Europe: Norway (Statnett NVF 2025), Poland (PSE Wymogi 2025), Romania (Transelectrica/ANRE storage norm), Spain (P.O. 12.3), Sweden (EIFS 2018:2), Switzerland (Swissgrid CESS minimum), and 13 more