UK G99 (Type A-C) ride-through requirements

Low-voltage ride-through, Frequency ride-through for the United Kingdom. Every breakpoint below is read from the code itself, and where a point was taken off a published figure rather than stated in the clause, the section under that chart says so — an envelope that stops where its published chart stops.

2Envelopes
LVRT · FRTEvents
Distribution Connection level
below 110 kV Applicability boundary
LVRT

What is the low-voltage ride-through envelope for UK G99 (Type A-C)?

The plant must ride through for any voltage that stays on or above this envelope. The envelope holds 0.1 pu from t = 0 to 140 ms; then ramps linearly from 0.1 pu at 140 ms to 0.85 pu at 2.2 s; then 0.85 pu from 2.2 s, plotted to 3 min.

The clause states this boundary as a line; intermediate points are interpolated between its stated vertices. The envelope stops where the published chart stops; the code states no end time.

Applies to Type C-D power park modules connected below 110 kV (Table 13.5; includes ≥50 MW Type D)

UK G99 (Type A-C) — low-voltage ride-through envelopeUK G99 (Type A-C) low-voltage ride-through envelope. The plant must ride through for any voltage that stays on or above the line; below it, the envelope no longer applies. Logarithmic time axis from 0.01 s to 300 s; linear voltage axis in per-unit. The first band applies from the instant of the event (t = 0). The envelope holds 0.1 pu from t = 0 to 140 ms; then ramps linearly from 0.1 pu at 140 ms to 0.85 pu at 2.2 s; then 0.85 pu from 2.2 s, plotted to 3 min. Stops where the published chart stops — the code states no end time.UK G99 (Type A-C) — low-voltage ride-through envelopeStops where the published chart stops — the code states no end timenominal 1.00 pu0.010.11101000.000.200.400.600.801.001.20Time from event start (s, log scale) · first band applies from t = 0Voltage (pu)0.85 puplotted to 3 minMUST RIDE THROUGHmust ride through on or above the lineends at the plotted window, not a stated limit
Low-voltage ride-through envelope for UK G99 (Type A-C). Time runs on a logarithmic axis, so the ramp — a straight line in real time — only looks curved here. Scroll the chart sideways for the rest of the time axis →
Low-voltage ride-through breakpoints for UK G99 (Type A-C)
From To Voltage Between the points
0 140 ms 0.1 pu Held flat
140 ms 2.2 s 0.1 → 0.85 pu Ramps linearly
2.2 s plotted to 3 min 0.85 pu Held flat
The clause this came from

ENA EREC G99 Issue 2, 10 March 2025, Table 13.5 and Figure 13.10 'Voltage against time curve applicable to Type C and Type D Power Park Modules connected below 110 kV': Uret 0.1, Uclear 0.10, Urec1 0.10, Urec2 0.85; tclear 0.14, trec1 0.14, trec2 0.14, trec3 2.2 (figure axis extends to 180 s). Identical to Table 12.2 / Figure 12.6 for Type B PPMs. Type A: clause 11.3.1. The code defines a linear recovery ramp; the vertices are read from the clause and the chart draws the segment between them.

FRT

What is the frequency ride-through envelope for UK G99 (Type A-C)?

The plant must ride through between the upper and lower bands. The upper (over-frequency) band holds 52 Hz from t = 0 to 15 min; then 51.5 Hz from 15 min to 90 min; then 51 Hz from 90 min onward — the last band the envelope defines, with no stated end time. The lower (under-frequency) band holds 47 Hz from t = 0 to 20 s; then 47.5 Hz from 20 s to 90 min; then 49 Hz from 90 min onward — the last band the envelope defines, with no stated end time.

The last band has no stated end time. The clause below states a continuous region — highlighted; check which band it covers, because it is not always the last one.

Applies to Type A-C power park modules connected below 110 kV

UK G99 (Type A-C) — frequency ride-through envelopeUK G99 (Type A-C) frequency ride-through envelope. The plant must ride through for any frequency that stays between the lower and upper bands. Logarithmic time axis from 1 s to 20000 s; linear frequency axis in hertz. The first band applies from the instant of the event (t = 0). upper (over-frequency) band: holds 52 Hz from t = 0 to 15 min; then 51.5 Hz from 15 min to 90 min; then 51 Hz from 90 min onward — the last band the envelope defines, with no stated end time (drawn as an open dashed tail). lower (under-frequency) band: holds 47 Hz from t = 0 to 20 s; then 47.5 Hz from 20 s to 90 min; then 49 Hz from 90 min onward — the last band the envelope defines, with no stated end time (drawn as an open dashed tail).UK G99 (Type A-C) — frequency ride-through envelopenominal 50 Hz1101001000100004647484950515253Time from event start (s, log scale) · first band applies from t = 0Frequency (Hz)51 Hz49 HzMUST RIDE THROUGHUpper band (over-frequency)Lower band (under-frequency)must ride through between the bandsopen — no stated end time
Frequency ride-through envelope for UK G99 (Type A-C). Time runs on a logarithmic axis. Scroll the chart sideways for the rest of the time axis →

Upper limit

Frequency ride-through breakpoints for UK G99 (Type A-C) — Upper limit
From To Frequency Between the points
0 15 min 52 Hz Held flat
15 min 90 min 51.5 Hz Held flat
90 min no stated end 51 Hz Held flat

Lower limit

Frequency ride-through breakpoints for UK G99 (Type A-C) — Lower limit
From To Frequency Between the points
0 20 s 47 Hz Held flat
20 s 90 min 47.5 Hz Held flat
90 min no stated end 49 Hz Held flat
The clause this came from

ENA EREC G99 Issue 2 (2025), clause 13.2.1 (and identically 11.2.1, 12.2.1): '(a) 47 Hz - 47.5 Hz Operation for a period of at least 20 s'; '(b) 47.5 Hz - 49.0 Hz ... at least 90 minutes'; '(c) 49.0 Hz - 51.0 Hz Continuous operation'; '(d) 51.0 Hz - 51.5 Hz ... at least 90 minutes'; '(e) 51.5 Hz - 52 Hz ... at least 15 minutes'.

Scope

Who does UK G99 (Type A-C) bind, and since when?

Type C-D power park modules connected below 110 kV (Table 13.5; includes ≥50 MW Type D). No date of effect is published here — grid codes are reissued, so check the current issue before relying on it.

These figures are a reading aid, not legal advice. Grid codes are reissued: verify against the current edition before you design to them.

Digitised operating parameters beyond ride-through — droop, reactive capability, operating ranges — are published for 36 of the 66 codes in this atlas, not yet for UK G99 (Type A-C). That is a gap on this site, not a statement that UK G99 (Type A-C) sets none — the atlas hub marks the codes that carry them.

Curve data last checked against the code on — 66 standards, 130 envelopes, published by bess.engineer under CC BY 4.0.

Questions

Questions this page answers about UK G99 (Type A-C)

Does UK G99 (Type A-C) require ride-through, or only that the plant does not trip?
Ride-through. Every envelope on this page is a performance duty the plant must meet, not a protection-setting no-trip boundary — they are different obligations. That is what these curves are; they are not everything UK G99 (Type A-C) contains. The requirement sentence under each chart says which side of the curve is the compliant one.
Are the numbers on this page taken from UK G99 (Type A-C) itself?
Every breakpoint is read from the code, and where a point was taken off a published figure rather than stated in the clause, the section under that chart says so — on this page that includes an envelope that stops where its published chart stops. The clause each curve came from is quoted under it.
Which events are charted for UK G99 (Type A-C)?
UK G99 (Type A-C) is charted here with 2 envelopes — low-voltage ride-through, frequency ride-through (LVRT, FRT). No high-voltage envelope is charted here — check UK G99 (Type A-C) itself before concluding it sets none.
Related

Ride-through, in context.

An envelope is a compliance boundary; understanding why it exists is a different question. The ride-through and grid-forming entries cover the engineering, and the Engineering Foundations course builds it from the physics up.

Also for the United Kingdom: UK G99 (Type D)

Elsewhere in Europe: Norway (Statnett NVF 2025), Poland (PSE Wymogi 2025), Romania (Transelectrica/ANRE storage norm), Spain (P.O. 12.3), Sweden (EIFS 2018:2), and 13 more