Colombia (CREG 060/2019) ride-through requirements

Low-voltage ride-through, High-voltage ride-through for Colombia. Every breakpoint below is read from the code itself, and where a point was taken off a published figure rather than stated in the clause, the section under that chart says so — an envelope that stops where its published chart stops.

2Envelopes
LVRT · HVRTEvents
Transmission Connection level
STN/STR, 500 kV excluded Applicability boundary
LVRT

What is the low-voltage ride-through envelope for Colombia (CREG 060/2019)?

The plant must ride through for any voltage that stays on or above this envelope. The envelope holds 0 pu from t = 0 to 150 ms; then ramps linearly from 0 pu at 150 ms to 0.1 pu at 500 ms; then ramps linearly from 0.1 pu at 500 ms to 0.85 pu at 1.5 s; then 0.85 pu from 1.5 s to 20 s; then 0.9 pu from 20 s, plotted to 21 s.

The clause states this boundary as a line; intermediate points are interpolated between its stated vertices. The envelope stops where the published chart stops; the code states no end time.

Applies to Wind + PV plants on the STN/STR, 500 kV excluded

Colombia (CREG 060/2019) — low-voltage ride-through envelopeColombia (CREG 060/2019) low-voltage ride-through envelope. The plant must ride through for any voltage that stays on or above the line; below it, the envelope no longer applies. Logarithmic time axis from 0.01 s to 30 s; linear voltage axis in per-unit. The first band applies from the instant of the event (t = 0). The envelope holds 0 pu from t = 0 to 150 ms; then ramps linearly from 0 pu at 150 ms to 0.1 pu at 500 ms; then ramps linearly from 0.1 pu at 500 ms to 0.85 pu at 1.5 s; then 0.85 pu from 1.5 s to 20 s; then 0.9 pu from 20 s, plotted to 21 s. Stops where the published chart stops — the code states no end time.Colombia (CREG 060/2019) — low-voltage ride-through envelopeStops where the published chart stops — the code states no end timenominal 1.00 pu0.010.11100.000.200.400.600.801.001.20Time from event start (s, log scale) · first band applies from t = 0Voltage (pu)0.9 puplotted to 21 sMUST RIDE THROUGHmust ride through on or above the lineends at the plotted window, not a stated limit
Low-voltage ride-through envelope for Colombia (CREG 060/2019). Time runs on a logarithmic axis, so the ramp — a straight line in real time — only looks curved here. Scroll the chart sideways for the rest of the time axis →
Low-voltage ride-through breakpoints for Colombia (CREG 060/2019)
From To Voltage Between the points
0 150 ms 0 pu Held flat
150 ms 500 ms 0 → 0.1 pu Ramps linearly
500 ms 1.5 s 0.1 → 0.85 pu Ramps linearly
1.5 s 20 s 0.85 pu Held flat
20 s plotted to 21 s 0.9 pu Held flat
The clause this came from

Resolución CREG 060 de 2019, Artículo 14 (modifica numeral 5.7 lit. c) del Código de Operación), figura 'Característica de LVRT y HVRT para plantas eólicas y solares fotovoltaicas con conexión a STN y STR (no incluye 500 kV)' — verified from the official embedded graphic resolucion_creg_0060_2019_obj_2.gif. The code defines a linear recovery ramp; the vertices are read from the clause and the chart draws the segment between them.

HVRT

What is the high-voltage ride-through envelope for Colombia (CREG 060/2019)?

The plant must ride through for any voltage that stays on or below this envelope. The envelope holds 1.2 pu from t = 0 to 2 s; then 1.1 pu from 2 s onward — the last band the envelope defines, with no stated end time.

Every breakpoint is stated in the clause cited below.

Applies to Wind + PV plants on the STN/STR, 500 kV excluded

Colombia (CREG 060/2019) — high-voltage ride-through envelopeColombia (CREG 060/2019) high-voltage ride-through envelope. The plant must ride through for any voltage that stays on or below the line; above it, the envelope no longer applies. Logarithmic time axis from 0.1 s to 10 s; linear voltage axis in per-unit. The first band applies from the instant of the event (t = 0). The envelope holds 1.2 pu from t = 0 to 2 s; then 1.1 pu from 2 s onward — the last band the envelope defines, with no stated end time (drawn as an open dashed tail).Colombia (CREG 060/2019) — high-voltage ride-through envelopenominal 1.00 pu0.11100.20.5250.951.001.051.101.151.201.25Time from event start (s, log scale) · first band applies from t = 0Voltage (pu)1.1 puMUST RIDE THROUGHmust ride through on or below the lineopen — no stated end time
High-voltage ride-through envelope for Colombia (CREG 060/2019). Time runs on a logarithmic axis. Scroll the chart sideways for the rest of the time axis →
High-voltage ride-through breakpoints for Colombia (CREG 060/2019)
From To Voltage Between the points
0 2 s 1.2 pu Held flat
2 s no stated end 1.1 pu Held flat
The clause this came from

Resolución CREG 060 de 2019, Artículo 14 — numeral 5.7 lit. c) del Código de Operación; figura 'Característica de LVRT y HVRT ... con conexión a STN y STR (no incluye 500 kV)' (official graphic obj_2.gif).

Scope

Who does Colombia (CREG 060/2019) bind, and since when?

Wind + PV plants on the STN/STR, 500 kV excluded. No date of effect is published here — grid codes are reissued, so check the current issue before relying on it.

These figures are a reading aid, not legal advice. Grid codes are reissued: verify against the current edition before you design to them.

Digitised operating parameters beyond ride-through — droop, reactive capability, operating ranges — are published for 36 of the 66 codes in this atlas, not yet for Colombia (CREG 060/2019). That is a gap on this site, not a statement that Colombia (CREG 060/2019) sets none — the atlas hub marks the codes that carry them.

Curve data last checked against the code on — 66 standards, 130 envelopes, published by bess.engineer under CC BY 4.0.

Questions

Questions this page answers about Colombia (CREG 060/2019)

Does Colombia (CREG 060/2019) require ride-through, or only that the plant does not trip?
Ride-through. Every envelope on this page is a performance duty the plant must meet, not a protection-setting no-trip boundary — they are different obligations. That is what these curves are; they are not everything Colombia (CREG 060/2019) contains. The requirement sentence under each chart says which side of the curve is the compliant one.
Are the numbers on this page taken from Colombia (CREG 060/2019) itself?
Every breakpoint is read from the code, and where a point was taken off a published figure rather than stated in the clause, the section under that chart says so — on this page that includes an envelope that stops where its published chart stops. The clause each curve came from is quoted under it.
Which events are charted for Colombia (CREG 060/2019)?
Colombia (CREG 060/2019) is charted here with 2 envelopes — low-voltage ride-through, high-voltage ride-through (LVRT, HVRT). No frequency envelope is charted here — check Colombia (CREG 060/2019) itself before concluding it sets none.
Related

Ride-through, in context.

An envelope is a compliance boundary; understanding why it exists is a different question. The ride-through and grid-forming entries cover the engineering, and the Engineering Foundations course builds it from the physics up.

Also for Colombia: Colombia (CREG 060/2019, red de 500 kV)

Elsewhere in South America: Brazil (ONS Submódulo 2.10), Chile (NTSyCS), Ecuador (ARCONEL-001/24 Código de Conexión), Panama (Código de Redes Fotovoltaico 2017), Peru (COES PR-20, Anexo 1 Cap. 4), and 2 more