What a battery can sell
What ancillary services can a battery sell in Wholesale Electricity Market (WEM)?
Wholesale Electricity Market (WEM) has 5 ancillary-service products, across 4 families — regulation, contingency reserve, inertia & system strength and emergency control: Contingency Reserve Lower, Contingency Reserve Raise, Regulation Lower, Regulation Raise, Rate of Change of Frequency Control Service. Response timing, direction and eligibility for each are in the cards below, as the official sources state them.
Facts below are stated as the official sources state them. A missing line means the
source does not state that value — never that the value is zero.
Regulation
-
Regulation Lower REG_LOWER
operational
Frequently adjust injection or withdrawal under central control to lower SWIS frequency toward the Frequency Operating Standard.
- Direction
- lower generation; raise load
- Expected within
- 5 seconds
- Trigger / range
- AEMO AGC desired-MW signal; no fixed public frequency threshold.
- Eligibility
- AEMO-accredited facilities meeting AGC, SCADA, communication and performance requirements.
- Typical procurement
- AEMO calculates interval-specific requirements.
Five seconds is maximum communication/control response lag, not full activation. Full activation and hold depend on accredited capability and dispatch.
-
Regulation Raise REG_RAISE
operational
Frequently adjust injection or withdrawal under central control to raise SWIS frequency toward the Frequency Operating Standard.
- Direction
- raise generation; lower load
- Expected within
- 5 seconds
- Trigger / range
- AEMO AGC desired-MW signal; no fixed public frequency threshold.
- Eligibility
- AEMO-accredited facilities meeting AGC, SCADA, communication and performance requirements.
- Typical procurement
- AEMO calculates interval-specific requirements under the ESS Quantities Procedure.
Five seconds is the maximum communication/control response lag from receipt of the AEMO signal, not a universal full-ramp deadline. Full activation and hold depend on accredited ramp capability and dispatch.
Contingency reserve
-
Contingency Reserve Lower CR_LOWER
operational
Hold rapid downward response to contain frequency after a credible over-frequency contingency.
- Direction
- lower generation; raise load
- Sustain
- at least 15 min
- Trigger / range
- Automatic frequency-sensitive response after a contingency; facility-specific settings are accredited.
- Eligibility
- AEMO-accredited facilities meeting contingency response tests.
- Typical procurement
- Dynamic requirement under the ESS Quantities Procedure.
No single market-wide full-activation deadline; accredited response capability applies. Sustain requirement is at least 15 minutes.
Inertia & system strength
-
Rate of Change of Frequency Control Service ROCOF
operational
Provide inertia or inertia-equivalent capability that limits the initial rate of change of SWIS frequency after a contingency.
- Direction
- symmetric
- Full activation
- 0 s
- Trigger / range
- Inherent instantaneous response to RoCoF following a disturbance; no dispatch trigger threshold.
- Eligibility
- Facilities accredited for synchronous inertia or qualifying equivalent response under ESM Rules and procedures.
- Typical procurement
- Requirement is expressed through system inertia/RoCoF constraints, not a stable MW volume.
The service is procured as inertia contribution rather than an activated MW step, so there is no sustain duration to state.
Emergency control
-
Contingency Reserve Raise CR_RAISE
operational
Hold rapid upward response to contain frequency after a credible contingency and avoid under-frequency load shedding.
- Direction
- raise generation; lower load
- Sustain
- at least 15 min
- Trigger / range
- Automatic frequency-sensitive response after a contingency; facility-specific droop/block settings are accredited.
- Eligibility
- Accredited generation, storage or interruptible load; minimum certified response and technical tests apply.
- Typical procurement
- Dynamic Frequency Control Model quantity based on credible contingency size, inertia and facility performance.
No single market-wide full-activation deadline. Accreditation assigns a Facility Speed Factor from accepted bands 0.2, 0.5, 1, 3, 6, 10 or 15 seconds; the response must be sustainable for at least 15 minutes.