Why a 100 MWh Battery Delivers Less to the Grid

Ep. 8 3:00

About this episode

A battery starts with 100 MWh. In this worked example, 88.97 MWh reaches the grid meter. Follow the energy from the cells to the meter and see why 5 MWh held in reserve is different from the 6.03 MWh consumed by auxiliary loads or lost along the electrical path.

In Episode 8 of BESS Decoded, see how the usable state-of-charge (SOC) window, cell discharge losses, DC cables, power conversion system (PCS), AC cables, transformers and auxiliary loads such as cooling affect net energy export.

THE 100 MWh EXAMPLE

  • 5 MWh stays in the battery outside the usable SOC window.
  • 6.03 MWh goes to electrical and conversion losses and auxiliary consumption.
  • 88.97 MWh reaches the grid meter as net exported energy.

The example covers one discharge. Round-trip efficiency also includes charging. When comparing a BESS specification or supplier quote, check where the energy is measured and which losses the quoted figure already includes.

Terms in this episode

  • The MWh a plant can physically deliver at a stated boundary under the conditions in force — usable DC energy net of conversion, collection and auxiliary losses. Capability, not the contracted guarantee.

  • Where in the power path a power, energy, or efficiency figure is defined — cell, DC bus, PCS terminals, or POI. Numbers quoted at different boundaries cannot be compared.

  • The rated capacity at the start of life. Usable and contract energy are always lower.

  • The DC-side energy the SOC window lets the plant cycle — always less than nameplate, and before the losses on the way to the meter.

  • The permitted band of state of charge the BMS lets the system operate across. Its width — not nameplate — sets usable energy.

  • Energy out divided by energy in over a full cycle, after all losses. The boundary matters — gross vs. net.

  • Resistive heating in any current path — dissipated power is current squared times resistance, so twice the current makes four times the heat. The scaling law behind high-voltage design, cable loss budgets and the rate-dependent share of round-trip losses.

  • On-site power drawn by HVAC, controls, and the BMS. It reduces net round-trip efficiency and usable output.